Gas Turbine Type L20-A
Electrical power | 18.500 kW |
Fuel input | 53.899 kW |
Efficiency | 34,3% |
Exhaust gas mass flow | 59,81 kg/s |
Exhaust gas temperature | 542°C |
Generator Voltage | 10,5 kV |
Steam mass flow 8 bar(g) saturated | 37,0 t/h |
Fuel type | Natural Gas |
Emissions | NOx: 15 ppm CO: 25 ppm |
Performance under ISO-conditions w/o duct losses at Generator Terminal |